The article explains the different error codes that may appear on Westpoint air conditioners and what they mean. It provides a comprehensive list of error codes and their possible causes, including sensor malfunctions, power issues, and refrigerant leaks.
Codes Table
Error Codes | Problem |
---|---|
C1 | Arc control |
C2 | Electrical leakage protection |
C5 | Jumper cap error |
EH | Auxiliary electrical heater error |
E0 | Water pump error |
E1 | High pressure protection of the compressor |
E2 | Anti-freezing protection of the indoor unit |
E3 | Low pressure protection of the compressor |
E4 | High discharge temperature protection of the compressor |
E5 | Overload protection of the compressor |
E6 | Communication error |
E8 | Indoor unit fan protection |
E9 | Water overflow protection |
F0 | Indoor ambient temperature sensor error at the return air inlet. |
F1 | Evaporator temperature sensor error |
F2 | Condenser temperature sensor error |
F3 | Indoor ambient temperature sensor error |
F4 | Discharge temperature sensor error |
F5 | Ambient temperature sensor error at the display |
FF | Sub-room switch opened |
Rooftop Codes
Error Codes | Problem |
---|---|
E0 | Compressor phase sequence error or phase default |
E1 | Outdoor coil sensor in sys. A error |
E2 | Outdoor coil sensor in sys. B error |
E3 | Overcurrent protection of system A are active 3 times within one hour. |
E4 | Overcurrent protection of systemB are active 3 times within one hour. |
E5 | Indoor coil sensor in sys. A error |
E6 | Indoor coil sensor in sys. B error |
E7 | High-Low pressure protection or discharge temperature protection of system A reached 3 times |
E8 | High-Low pressure protection or discharge temperature protection of system B reached 3 times |
E9 | Indoor sensor error |
EA | Outdoor ambient sensor error |
Eb | Wire controller output error |
P0 | Overcurrent protection in sys. A |
P1 | Overcurrent protection in sys. B |
P2 | Overcurrent protection for indoor fan |
P3 | Comprehensive protection for outdoor fan |
P4 | Protection for Hi/Lo pressure or exhause temp. in sys.A |
P5 | Protection for Hi/Lo pressure or exhauset temp. in sys.B |
P6 | Hi-pressure protection initiated in T2 evaporator stops the outdoor unit fan |
P7 | Hi-pressure protection initiated in T2 evaporator stops the outdoor unit fan and compressor |
P8 | Protection for condenser Hi-temp in sys A. |
P9 | Protection for condenser Hİ-temp in sys B. |
Pc | Anti-freezing protection for evaporator in sys. A |
Pd | Anti-freezing protection for evaporator in sys. B |
dF | Defrosting |
PA | Protection for outdoor temp |
Troubleshooting
Before calling for service, review this list. It may save you time and expense. This list includes common occurrences that are not the result of defective workman-ship or materials in this appliance.
Problem: Air conditioner does not start
Solution:
- Wall plug disconnected. Push plug firmly into wall outlet.
- House fuse blown or circuit breaker tripped. Replace fuse with time delay type or reset circuit breaker.
- Plug Current Device Tripped. Press the RESET button.
- Control is OFF. Turn Control ON and set to desired setting.
Problem: Air from unit does not feel cold enough.
Solution:
- Room temperature below 17 C(62 F). Cooling may not occur until room temperature rises above 17 C(62 F).
- Temperature sensing element touching cold coil, located behind air filter. Straighten tube away from coil.
- Reset to a Lower temperature.
- Compressor shut-off by changing modes. Wait approximately 3 minutes and listen for compressor to restart when set in the COOL mode.
Problem: Air conditioner cooling, but room is too warm- ice forming on cooling coil behind decorative front.
Solution:
- Outdoor temperature below 18 C(64 F). To defrost the coil, set FAN ONLY mode.
- Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set to FAN ONLY mode.
- Thermostat set too cold for night-time cooling. To defrost the coil, set to FAN ONLY mode. Then, set temperature to a Higher setting.
Problem: Air conditioner cooling, but room is too warm- NO ice forming on cooling coil behind decorative front.
Solution:
- Dirty air filter- air restricted. Clean air filter. Refer to Care and Cleaning section.
- Temperature is set too High, set temperature to a Lower setting.
- Air directional louvers positioned improperly. Position louvers for better air distribution.
- Front of units is blocked by drapes, blinds, furniture, etc. – restricts air distribution. Clear blockage in front of unit.
- Doors, windows, registers, etc. Open- cold air escapes. Close doors, windows, registers.
- Unit recently turned on in hot room. Allow additional time to remove Stored heat from walls, ceiling, floor and furniture.
Problem: Air conditioner turns on and off rapidly
Solution:
- Dirty air filter- air restricted. Clean air filter.
- Outside temperature extremely hot. Set FAN speed to a Higher setting to bring air past cooling coils more frequently.
Problem: Noise when unit is cooling
Solution:
- Air movement sound. This is normal . If too loud, set to a slower FAN setting.
- Window vibration – poor installation. Refer to installation instructions or check with installer.
Problem: Water dripping INSIDE when unit is cooling
Solution: Improper installation. Tilt air conditioner slightly to the outside to allow water drainage. Refer to installation instructions – check with installer.
Problem: Remote Sensing Deactivating Prematurely (some models)
Solution:
- Remote control not located within range. Place remote control within 20 feet & 180 , radius of the front of the unit.
- Remote control signal obstructed. Remove obstruction.
Remote Control
Manual
- Newair Portable AC Error Codes and Troubleshooting - December 20, 2024
- Sharp AC Error Codes and Troubleshooting - December 15, 2024
- Marq By Flipkart AC Error Codes List With Fixes - December 15, 2024
I wanna change my Westpoint from fahrenheit to Celsius. is any one known what should I do ???